1946
Varen er på lager.
Varen er bestilt fra leverandør og leveringsdato er bekreftet.
Varen er bestilt fra leverandør, men leveringsdato er ikke bekreftet.
Varen må bestilles fra leverandør.
Varen befinner seg på fjernlager.
Varen er bestilt fra leverandør, men leveringsdato er ikke bekreftet.
Varene bestilles fra vår leverandørs lager.
Ubekreftet - Ta kontakt med kundesenter for nærmere informasjon.

 Handlevogn

Handlevognen er tom.

 

Ex Cable Gland A2LBF-NP/20/M20 NP-Brass

IP66&IP68@25m EExdeIIC oø 9,4-14,0mm

Varenr:
A2LFNP20M20
A2LFNP20M20 Peppers A2LBF/NP/20/M20 Ex Cable Gland A2LBF-NP/20/M20 NP-Brass IP66&IP68@25m EExdeIIC oø 9,4-14,0mm
A2LFNP20M20 Peppers A2LBF/NP/20/M20 Ex Cable Gland A2LBF-NP/20/M20 NP-Brass IP66&IP68@25m EExdeIIC oø 9,4-14,0mm
Cable Gland Type A - (Single Compression for any Cable)  
 
 

    Ex d     Ex e      Ex nR   /   Ex tD A21   /   IP66   /   IP68     

 

  
 
  
“A” type glands, certified Flameproof Ex d, Increased Safety Ex e & Restricted Breathing Ex nR are suitable for use in Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC.
Commonly referred to as “stuffing glands” they provide a controlled pull resistant environmental displacement seal on the cable outer sheath, minimising damage to cables that exhibit “cold flow” characteristics. 
 

The gland maintains IP66 & IP68 to 25 metres and is deluge proof without the use of an additional seal or deluge boot.
It is supplied with an IP O-ring seal as standard on metric entry threads.
Options are available for use with LSOH cables and extreme temperature applications.
 
 
Compliance Standard:
EN 60079-0, EN 60079-1, EN 60079-7, EN 60079-15, EN 61241-0, EN 61241-1, IEC 60079-0, IEC 60079-1, IEC 60079-7, IEC 61241-0, IEC 61241-1 & IEC 60529
 
Certification:ATEXII 2 GD Ex d IIC / Ex e II / Ex tD A21
II 3 GD Ex nR II
IECExEx d IIC / Ex e II / Ex tD A21
GOST-REx d IICU / Ex e IIU
CSAEx d IIC / Ex e II Class I Zone 1
Class I Division 2, Groups A, B, C & D
Class II Division 2, Groups E, F & G
Class III, Enclosure Types 3, 4 & 4X
NEPSIEx d IIC / Ex e II
INMETROBR - Ex d IIC / Ex e II / Ex nR II / Ex tD A21
ABS1-1-4/7.7, 4.8-3/1.7, 4-8-3/13 and 4-8-4/27.5
MODURules 4-3-3/9
LLOYD’SEnclosure Systems (Part 1B)
RMRSPart XI of Rules for sea-going ships (ed.2008)
  
Cert. No.ATEXSIRA 01ATEX1272X &
SIRA 09ATEX1221X
IECExSIR 07.0096X
GOST-RPOCC GB.I606.B00853
CSACSA 1356011
NEPSIGYJ06186X
INMETRONCC 5879/09 X
ABS 09-LD463991-PDA
LLOYD’S10/00056
RMRS09.00784.011
 
      
IP Rating:IP66 & IP68 (25 metres - 30 minutes),
NEMA 4X & DTS01 1991
Operating
Temperature:Neoprene Seals -20ºC to +85ºC
Silicone Seals -60ºC to +180ºC
Materials:Brass, Stainless Steel or Aluminium
Plating:Nickel or Zinc
 
 
 

Cable Gland Selection Table:

 
GlandEntryThreadCableNominalDim.Weight
SizeThreadLengthAcceptanceProtrusionAcrossKgs.
Size[B]Range [D] Length [L]Corners [A]
  
16M16 x 1.5  16  4.0 - 8.4    33  28.00.076
16M20 x 1.5  16  4.0 - 8.4    33  28.00.078
20SM20 x 1.5  16  7.2 - 11.7    33  28.00.101
20M20 x 1.5  16  9.4 - 14.0    33  33.00.127
25M25 x 1.5  1613.5 - 20.0    33  41.40.166
32M32 x 1.5  1619.5 - 26.3    33  50.60.244
40M40 x 1.5  1623.0 - 32.2    37  60.50.396
50SM50 x 1.5  1628.1 - 38.2    37  71.50.558
50M50 x 1.5  1633.1 - 44.1    37  71.50.438
63SM63 x 1.5  1939.2 - 50.1    37  88.00.832
63M63 x 1.5  1946.7 - 56.0    37  88.00.664
75SM75 x 1.5  1952.1 - 62.0    37  99.00.924
75M75 x 1.5  1958.0 - 68.0    37  99.00.714
80M80 x 2  2562.2 - 72.0    50115.21.514
85M85 x 2  2569.0 - 78.0    50115.21.332
90M90 x 2  2574.0 - 84.0    50125.71.622
100M100 x 2  2582.0 - 90.0    50125.71.523

 
Alterativ Gland Size and Entry Thread Size in NPT:
 
Gland Size    Entry Thread Size NPT
  
   16050 NPT (1/2”) or 075 NPT (3/4”)
   20S050 NPT (1/2”) or 075 NPT (3/4”)
   20050 NPT (1/2”) or 075 NPT (3/4”)
   25075 NPT (3/4”) or 100 NPT (1”)
   32100 NPT (1”) or 125 NPT (1 1/4”)
   40125 NPT (1 1/4”) or 150 NPT (1 1/2”)
   50S150 NPT (1 1/2”) or 200 NPT (2”)
   50200 NPT (2”)
   63S200 NPT (2”) or 250 NPT (2 1/2”)
   63250 NPT (2 1/2”)
   75S250 NPT (2 1/2”) or 300 NPT (3”)
   75300 NPT (3”)
   80300 NPT (3”) or 350 NPT (3 1/2”)
   85300 NPT (3”) or 350 NPT (3 1/2”)
   90350 NPT (3 1/2”) or 400 NPT (4”)
100350 NPT (3 1/2”) or 400 NPT (4”)
 
 
  1
Part Numbers:      A   2  L  B  F
  3  S
  4  A
 
 
Example Part Numbering:  A 2 L B F C K 1 / N P / 2 0 / 0 5 0 N P T
(See below for details)
 
AType of gland featuring controlled displacement
sealing
2(2) Neoprene Seals (-20ºC to +85ºC)
(3) Silicone Seals (-60ºC to +180ºC)
(1) Neoprene/Lead
(4) Silicone/Lead
LPeppers Lightweight Design
B(B) Brass
(S) Stainless Steel
(A) Aluminium
FMultiple Certification
  
Options:C(C) PVC Shroud
Options:(P) PCP Shroud
Options:(3) LSOH Shroud
Options:K or V(K) Locknut & Nylon or (V) Fibre IP Washer
Options:TIncluding Earth Tag
Options:SIncluding Serrated Washer
Options:1Quantity per kit
Options:NP(NP) Nickel Plated or (ZP) Zinc Plated
  
20Gland shell size
050 NPT1/2” NPT Entry Thread
 
 
 Optional Accessories:
 
Locknut:Brass (A C B L N)
Brass Nickel Plated (A C B L N / N P)
Stainless Steel (A C S L N)
Aluminium  (A C A L N)
  
Earth tag:Brass (A C B E T)
Brass Nickel Plated (A C B E T / N P)
Stainless Steel (A C S E T)
Aluminium (A C A E T)
   
IP Washers:Nylon (A C N S W) (-40° to +95°C)
Fibre (A C F S W) (-40° to +135°C)
PTFE (A C P S W) (-200° to +260°C)
(see note 3 below)
  
Serrated Washers:Stainless Steel (A C S S W)
  
Shrouds:PVC (A C S P V C)  (-25° to +70°C)
PCP (A C S P C P) (-30° to +100°C)
LSOH (A C S S I O) (-60° to +200°C)
 

 
 Notes:
  1. Gland size does not necessarily equate to the entry thread size. Gland size 16 is also available with an M16 x 1.5 entry thread.
  2. The IP O-ring seal is only available on metric entry threads. IP washers can be supplied for tapered entry threads.
  3. Please ensure that the IP O-ring is not used in conjunction with a flat IP washer.
  4. Dimensions (A) & (B) may differ for glands with non metric entry threads. Please refer to our “Thread Reference Tables” for specific dimensions.
  5. Where glands are fitted into non-metallic Ex e enclosures they must be included within the earth circuit of the system.
  6. The user should seek expert advice if intending to combine flammable and combustible dust in one environment/installation.
  7. Assembly instructions (Manual) must be read prior to installation and adhered to in full.
  8. Peppers supplies cable glands with parallel entry threads that conform to the flameproof threaded joint requirements of IEC/EN 60079-1 and other equivalent standards.
    They usually incorporate a thread run out according to the available machining techniques and will not have a full form thread for the entire length.
    Peppers will not be held responsible for clients’ installations where this has not been taken into account.
  9. To maintain the specified IP rating, clearance holes must be in accordance with EN 50262 Table 1 and the entry device should be suitably secured.
  10. All gland kits supplied with silicone seals will include a PTFE IP washer in order to maintain the temperature range.

For further details, please refer to the attached Datasheet, Assembly Instructions (Manual), Certificates and other relevant documents.
 


Copyright © 2017 Marin Supply. All rights reserved.
Forretningssystem og netthandel er levert av MultiCase™ Norge AS
(3.16.12.37)